Form 6 triple-single microprocessor-based rack mount recloser control
20 INSTALLATION AND OPERATION INSTRUCTIONS   MN280084EN   July 2018
Customer connections for DC power and 
ACvoltagesensing
DC power
Wiring connections to the Form 6-TS rack mount recloser 
control are made to the back panel (Figure11). Input 
DCpower is required to power the control.
IMPORTANT
Verify the label on the Form 6-TS rack mount control matches 
the voltage of the substation supply prior toinstallation.
DC power is connected to terminal block TB2, terminal 
points 19(–) and 20(+) on the interface power module. 
Battery negative is not grounded at the control as the 
control should be grounded per the information in the 
Grounding the control section.
AC voltage sensing
Input AC power is required to provide the following functions:
 
Directional Protection
 
Sync Check Protection
 
Voltage Protection
 
Frequency Protection
 
Single- or Three-Phase Voltage and Power Metering
Figure12 illustrates customer connections to TB10,  
120 VAC Delta connection.
AC voltage input connections are connected to TB10 for 
Wye connections only. Figure13 illustrates three-phase 
wiring connections for source and load side connections.
The AC voltage inputs for both source or load side accept a 
voltage input of 120 VAC nominal.
For single-phase source side AC voltage inputs, connections 
to AØ, BØ, or CØ are acceptable.
For single-phase load side AC voltage inputs, connections  
to XØ, YØ, or ZØ are acceptable.
The following are not functional for single-phase  
AC voltage input:
 
Directional Protection
 
Single-Phase Voltage Protection
 
True Three-Phase Metering
ote:N Phantom Phase can generate missing phases for 
three-phase metering estimates.
V(1-2)
V(3-4) V(5-6)
TB10
VOLTAGE SENSING
CØ
BØ
AØ
DISCONNECT
SWITCHES
(customer-supplied)
Figure12.  Customer connections to TB10, 120 VAC delta connection
ote:N Terminal Block positions 
TB10-V1 and TB10-V6 are 
factory-jumpered together.
  Terminal Block positions 
TB10-V2 and TB10-V3 are 
factory-jumpered together.
  Terminal Block positions 
TB10-V4 and TB10-V5 are 
factory-jumpered together.