Form 6 triple-single microprocessor-based rack mount recloser control
34 INSTALLATION AND OPERATION INSTRUCTIONS MN280084EN July 2018
Return the control to service
WARNING
This equipment is not intended to protect human
life. Follow all locally approved procedures and safety
practices when installing or operating this equipment.
Failure to comply can result in death, severe personal
injury and equipment damage. G102.1
After the required work or testing is completed, follow this
procedure to return the control to service:
CAUTION
Equipment misoperation. Do not connect this control
to an energized recloser until all control settings have
been properly programmed and verified. Refer to the
programming information for this control. Failure to
comply can result in control and recloser misoperation,
equipment damage, and personal injury. G110.3
1. Verify that all control settings are correct prior to
installation.
WARNING
Hazardous voltage. Recloser and control must be solidly
grounded. Follow all locally approved procedures and
safety practices when grounding this equipment. Improper
grounding can result in contact with high voltage, which
will cause death or severe personal injury. G115.1
2. Connect the ground to the control.
ote:N Refer to Grounding the control section.
3. Use a screwdriver to connect all wiring on terminal block
TB2 (Figure27) to the control in this specific order:
A. First connect TB2-1 through TB2-17.
B. Then connect TB2-19 and TB2-20 (voltage inputs).
4. Connect any serial communications ports and IRIG-B
timing connection (Figure27).
5. Connect any control input and status output wiring to
TB1, TB3, and TB4 (Figure27).
6. Use a screwdriver to connect all wiring on terminal
blocks TB10 and TB11 to the control.
7. Connect control AC sensing voltage to the control via
disconnect switches.
ote:N Refer to Customer connections for DC power
and ACvoltagesensing section.
8. Connect DC power to the control via disconnect
switches.
ote:N Refer to Customer connections for DC power
and ACvoltagesensing section.
9. Reconnect CT circuit by unshorting secondaries from
the CT shorting-type terminal block.
CAUTION
Hazardous voltage. Open CT secondaries can generate
high voltages. Contact with CT pins of the disconnected
cable can cause electric shock and may result in personal
injury. Open recloser contacts and open disconnect
switches before disconnecting control cable. T204.3
10. The recloser and control are ready for service. Once
installed, remove bypass switches on the recloser.
11. Disable GND TRIP BLOCKED.
A. Press the CHANGE button on the Operator Panel
to enter the CHANGE mode.
B. Depress the GND TRIP BLOCKED button within
ten seconds after entering the CHANGE mode.
ote:N If the GND TRIP BLOCK button is not depressed
within ten seconds, the function is not activated.
TB1
1
2
3 57911 13 15 17 19
46 81012141618
CI1
CI2 CI3 SS1 CO1
CO2 CO3
CO4
CI4
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
TB3
1
3
579111315171921
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
TB4
2
46 81012141618
20
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
CO6
13
5
7911 13
CO7 CO8
CO9 CO10 CO11
CO12
2
46 81012
CO7 CO8 CO9 CO10 CO11CO12
FUSE
(10 AMP)
FUSE
(10 AMP)
TB5
+
1
-
5
2
-
4
+
INPUT POWER AUXILIARY POWER
28 VDC
TB2
1234 5 6789101112131415161718
19 20
Three Control Input and Five Status
Output Contacts (Standard Feature)
Eight Control Inputs
and Eight Status
Outputs (Accessory)
Terminal Block for
Connecting to Recloser(s)
via Junction Box
J1-RS-232
IRIG-B
RS-485
RS-232 DTE
RS-232 Serial Communication Port
RS-485 Serial Communication
Port (optional), Fiber Optic port,
"ST" Type Connector (optional),
Ethernet Port, "MT-RJ" Fiber
RJ45 Connector (optional)
C + –
IRIG-B Time Sync Connector
P1
P2
P3
P4
VOLTAGE SENSING
53VDC CONTROL CABLE 28 VAC
FUSE
(10 AMP)
FUSE
(10 AMP)
TB12
+
1
-
5
2
-
4
+
TB9
+
–
28 VDC
WHETTING VOLTAGE
+
–
48/125 VDC
Customer Connections
Voltage Inputs
CONTROL CABLE
FUSE
(10 AMP)
FUSE
(10 AMP)
TB13
+
1
-
5
2
-
4
+
V(1-2)
V(3-4) V(5-6)
TB10
VOLTAGE SENSING
TB11
Customer Connections
Source AC Voltage Sensing
(AØ, BØ, CØ)
Customer Connections
Load AC Voltage Sensing
(XØ, YØ, ZØ)
TB5, TB12, TB13, P1, P3, and P4 are factory-wired connections only.
Interface Power Module
Control Module
Factory
Wiring
Port
V(1-2)
V(3-4) V(5-6)
VOLTAGE SENSING
Figure27. Back of Form 6-TS rack mount recloser control