Form 6 triple-single microprocessor-based rack mount recloser control
22 INSTALLATION AND OPERATION INSTRUCTIONS   MN280084EN   July 2018
Standard default supervisory input control and 
output status contacts
The standard Form 6 Triple-Single rack mount recloser 
control includes three control contact inputs and five 
status contact outputs. The standard default I/O terminal 
connections are identified in Figure14. A discrete interface 
board accessory is available if additional I/O is required. The 
accessory includes eight control contact inputs and eight 
status outputs as identified in Figure15.
All of the control inputs and status outputs are user-
configurable via the Idea Workbench. To avoid configuration 
time, the most common control inputs and status outputs 
are included as default values. Refer to Figure13 and 
Figure14 and Table5, Table6, and Table7. Refer to 
Service Information S280-70-9 (ProView 4.X.X) or S280-70-
23 (ProView 5.X.X) Form 6-TS Control Programming Guide 
for additional information.
NOTICE
External leads must be shielded and the shield must 
be grounded at both ends. Terminate each lead with 
a320VAC, 150 Joules metal oxide varistor (MOV), or 
equivalent, at the remote end. Attach MOVs between 
the leads and ground. Failure to properly shield and 
protect leads can result in equipment damage and/or 
unintentionaloperation.
IMPORTANT 
Shielding and Surge Protection of Supervisory Cables 
All supervisory operation and control monitor leads must 
be protected within shielded cables. Refer to Figure16 or 
Figure17 as appropriate.
Table5.  Operating whetting voltage and current 
requirements for the standard (TB1) and accessory 
(TB3)discrete interface boards
Input voltage Nominal current Minimum   
operating time
9 VDC – 290 VDC,
7 VAC – 265 VAC 2.5 mA 5 milliseconds
Table6.  Ratings table for output status contacts  
CO1 through CO12 (TB1, TB3, and TB4)  
(resistive load – pickup time 8 ms, dropout 5 ms)
Input voltage Contact rating
120 VAC 8 A
12 VDC 8 A
24 VDC 8 A
48 VDC 1 A
125 VDC 0.4 A
Table7.  Ratings table for output status contact SS1 
(resistive load – pickup time 2 ms, dropout 15 ms) (TB1)
Input voltage Contact rating
120 VAC 8 A
12 VDC 8 A
24 VDC 8 A
48 VDC 8 A
125 VDC 8 A
Before placing the control and the  
recloser into service
 CAUTION
Equipment misoperation. Do not connect this control 
to an energized recloser until all control settings have 
been properly programmed and verified. Refer to the 
programming information for this control. Failure to 
comply can result in control and recloser misoperation, 
equipment damage, and personal injury.  G110.3
Prior to placing the control and recloser(s) into service, 
the following installation procedures must be properly 
completed and verified:
1.   Removable insert labels changed. (Not required – user-
preference option.)
ote:N Refer to Using removable inserts section in this 
manual for more information.
2.  NOVA-TS reclosers (3) installed according to all locally 
approved standards and practices.
3.  AC and DC disconnect switches installed.
4.  Control and reclosers properly grounded in accordance 
with guidelines in this manual and the appropriate 
recloser manual.
  Service Information MN280045EN NOVA-TS 
Recloser Installation and Operation Instructions
5.  Control wiring between control, junction box, and 
recloser(s) properly connected and supported.
6.  DC power and AC voltage sensing connected to 
thecontrol.
ote:N The control Power Save feature will turn off the 
backlit LCD display and all LEDs if no front panel 
keypad is pressed within ten minutes.
7.   All control programming entered and verified by 
appropriate personnel.
ote:N Refer to Service Information S280-70-9  
(ProView 4.X.X) or S280-70-23 (ProView 5.X.X) 
Form 6-TS Control Programming Guide for 
additional information.
8.  Customer connections for remote and supervisory 
operation checked and completed in accordance with 
proper shielding and surge protection.