Form 6 triple-single microprocessor-based rack mount recloser control
23INSTALLATION AND OPERATION INSTRUCTIONS MN280084EN July 2018
NOTICE
External leads must be shielded and the shield must
be grounded at both ends. Terminate each lead with
a320VAC, 150 Joules metal oxide varistor (MOV), or
equivalent, at the remote end. Attach MOVs between
the leads and ground. Failure to properly shield and
protect leads can result in equipment damage and/or
unintentionaloperation.
IMPORTANT
Shielding and Surge Protection of Supervisory Cables
All supervisory operation and control monitor leads must
be protected within shielded cables. Refer to Figure16 or
Figure17 as appropriate.
TB1
SS1
1
2
35
7
91113151719
4
68
10
12
14
16 18
CI1
CI2 CI3
SS1 CO1
CO2 CO3
CO4
CI1 CI2 CI3
CO1
CO2
CO3
CO4
Three-Phase Remote Trip and Lockout
Three-Phase Supervisory Trip and Lockout
Three-Phase Supervisory Close
AØ Control
Lockout
Status
(Not
Lockout)*
AØ Recloser
Status
(Recloser
Open)*
A
B
Hotline
Tag
Status
(Hotline
Tag Off)*
Control
OK
Status
(Control
Not OK)*
Ground Trip
Blocked
Status
(GRD TRIP
Normal)*
Customer Wiring
Remote/Supervisory Common
Customer-Supplied Voltage Inputs**
**Whetting voltage is also available from
the Form 6 Recloser Control on
Terminal Block TB9. Refer to Figure 17.
Note: Contact output relays revert to
de-energized positions as shown
upon downloading new schemes
or Workbench files.
*Relay Contacts shown
for Indicated Status
**Whetting voltage is also available from the
Form6 Recloser Control on Terminal Block TB9.
Refer to Figure16 or Figure17, as appropriate.
Figure14. Form 6-TS recloser control standard discrete interface board and default configurations. These default
contact input/outputs are completely configurable via the idea workbench