Form 6 triple-single microprocessor-based rack mount recloser control
33INSTALLATION AND OPERATION INSTRUCTIONS   MN280084EN   July 2018
Remove the control from service
IMPORTANT
Disconnect switches for both AC and DC circuits and 
a current transformer shorting-type terminal block are 
necessary to isolate the Form 6 recloser control for testing 
and servicing. 
1.   Enable GND TRIP BLOCKED to allow for ground trip to 
be disabled when re-energized.
A.  Press the CHANGE button on the Operator Panel 
to enter the CHANGE mode.
B.  Depress the GND TRIP BLOCKED button within 
ten seconds after entering the CHANGE mode.
ote:N If the GND TRIP BLOCK button is not depressed 
within ten seconds, the function is not activated.
2.  Remove DC power from the control using a separate 
disconnect switch.
3.  Remove control AC sensing voltage from the control 
using a separate disconnect switch.
4.  Use a screwdriver to disconnect all wiring on terminal 
blocks TB10 and TB11 from the control or use a 
customer-supplied disconnect switch.
 CAUTION
Hazardous voltage. Open CT secondaries can generate 
high voltages. Contact with CT pins of the disconnected 
cable can cause electric shock and may result in personal 
injury. Open recloser contacts and open disconnect 
switches before disconnecting control cable.  T204.3
5.  Short CT secondaries at a separate CT shorting-type 
terminal block.
6.  Remove any control input and status output wiring from 
TB1, TB3,  and TB4  (Figure7).
7.   Disconnect any serial communications ports and IRIG-B 
timing connection (Figure7).
8.  Use a screwdriver to disconnect all wiring on 
terminal block TB2 from the control (Figure7) in this 
specificorder:
A.  First disconnect TB2-19  and TB2-20  
(voltage inputs).
B.  Then disconnect TB2-1 through TB2-17.
ote:N Do not disconnect any of the three recloser 
cables from the reclosers or junction box unless 
all of the above steps have been completed. 
Refer to Service Information MN280045EN 
NOVA-TS Recloser Installation and Operation 
Instructions.
9.  Disconnect the ground from the control.
10.  Carefully transport the control to a suitable  
service facility.
Electrical testing of triple-single reclosers: NOVA-TS
 WARNING
Hazardous voltage. Solidly ground all equipment. Failure 
to comply can result in death, severe personal injury, 
and equipment damage.  T223.2
Each unit in the Type NOVA-TS Triple-Single recloser utilizes 
an interface circuit located in its mechanism housing. The 
electronic interface circuit controls the opening and closing 
signals to the magnetic actuator.
Figure26 shows a test circuit for NOVA-TS reclosers with 
the Form 6-TS control.
IMPORTANT
To ensure proper operation, always verify that the three 
cables between the junction box and the reclosers are 
connected when the control is in single-phase trip, three-
phase lockout mode or three-phase trip, three-phase lockout 
(ganged) mode.
Use this circuit to simulate load current and for testing 
minimum trip operation and sequencing the mechanism 
with the Form 6-TS control for each phase.
600:5
Recloser
BCT ON 600:5 Tap
2
115Vac
Variable
Autotransformer
   (10 Amp)
Clamp-On
Ammeter
Triple-Single
Junction Box
Use 2/0 cable or larger
1
2
3
4
5
6
Form 6-TS
Control
Source
Load
Figure26.  Suggested test circuit for NOVA-TS  
triple-single reclosers with form 6-TS control