EasyManua.ls Logo

Eaton Cutler-Hammer Easy-Start ES Series - Voltage Plugs and Jumper Settings

Eaton Cutler-Hammer Easy-Start ES Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Easy-Start ES Instruction Manual
Operation
SECTION 3
3-10
DIP Switch Settings
2. DIP Switch 3 (DS3)
DS3-1 Set to OPEN position for voltage
ramp mode.
Set to CLOSED position for current
ramp mode.
DS3-2 Set to OPEN position for energy
saving ON.
Set to CLOSED position for energy
saving OFF.
The DS3 switch is factory DS3-1 OPEN
set with: DS3-2 OPEN
3.
Voltage Plugs
The Easy-Start ES is shipped with two
voltage plugs in a separate envelope
packaged with the unit. The Easy-Start ES
will not operate until the appropriate voltage
plug is installed.
The plugs are stamped with voltage ratings
according to Table 3-13; and upon initial
inspection.
Notice - A voltage plug selected from Table
3-13, must be installed into the socket (J5) on
the logic board prior to start-up. (See Figure
4-14.)
There is also a jumper on the logic board that
must be in one of two positions. These
positions are marked LO HI. (See Figure
4-14.)
The jumper is factory installed in
the ā€œ
HI
ā€ position.
This jumper can remain in the HI position
except when operating at the lowest line
voltage rating of the two models rated:
208/230/460 and 460/500/575 volts. The
jumper is then moved to the LO position to
accommodate the low voltage end of the
voltage combination. Refer to Table 3-13 for
jumper positions.
Voltage Plugs and Jumper Positions
Table 3-13
EASY-START ES JUMPER
RATING LINE VOLTAGE PLUG TYPE POSITION
380/415 VAC 380V 380 HI
415V 415 HI
208/230/460 VAC 208V 230 LO
230V 230 HI
460V 460 HI
460/500/575 VAC 460V 500 LO
500V 500
HI
575V 575 HI
StockCheck.com

Table of Contents

Related product manuals