EasyManua.ls Logo

Eaton Cutler-Hammer Easy-Start ES Series - Page 89

Eaton Cutler-Hammer Easy-Start ES Series
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Easy-Start ES Instruction Manual
Options
SECTION 4
4-18
Application Notes
Smooth-Stop Option
The Smooth-Stop option is available with the
following variations:
Option ÒSÓ Printed circuit board with smooth-
stop pushbutton and wired relay
contact which opens the 120V ac
control to the logic board at the
end of the smooth stop.
Option ÒS1Ó Printed circuit board with smooth-
stop pushbutton and red light that
lights when the smooth-stop is
activated and goes out whenever
the smooth stop is completed.
Option ÒS2Ó Printed circuit board with smooth-
stop pushbutton, smooth-stop red
light, and a red light that lights
during ramp-up and goes out at
the end of ramp-up.
Check the product label on the Easy-Start ES to
confirm which option package was supplied.
The smooth-stop printed circuit board contains
the electronic logic for three different functions:
1. Smooth-Stop (1-30 seconds adjustable with
potentiometer SS time)
2. End of Ramp-Up Relay
3. Extended Time-Current; (End of Ramp-Up
DC Signal Voltage)
The input-output functions and relays are brought
out to the seven terminal blocks on the printed
circuit ÒSÓ option board:
(See Figure 4-16 for component layout.)
TB31-1, TB31-2 Input: Momentary N.O.
pushbutton for smooth-stop.
TB32-1, TB32-2 1A contact, N.O., closes during
smooth-stop.
TB33-1, TB33-2 N.C. contact, changes state at
end of smooth-stop.
TB33-2, TB33-3 N.O. contact, changes state at
end of smooth-stop.
TB34-1, TB34-2 N.C. contact, changes state at
end of smooth-stop.
TB34-2, TB34-3 N.O. contact, changes state at
end of smooth-stop.
TB35-1, TB35-2 N.C. contact, changes state at
end of ramp-up.
TB35-2, TB35-3 N.O. contact, changes state at
end of ramp-up.
TB36-1, TB36-2 N.C. contact, changes state at
end of ramp-up.
TB36-2, TB36-3 N.O. contact, changes state at
end of ramp-up.
TB37-1 output: +12V dc output at end of ramp-
up.
TB37-2 Logic Ground
Both smooth-stop and end of ramp-up option
functions can be turned on and off with one of
two switches on the option ÒSÓ printed circuit
board. These switches are identified as follows:
DS31-1 and DS31-2.
StockCheck.com