3.3 Installation and wiring connection diagram
EDX 60KVA/80KVA standard models feature single power input. The UPS can
be converted from single power source to dual power source by Eaton customer
service engineers on site. All operations should only be carried out by trained
service personnel authorised by Eaton.
Only connect the AC (3Φ4W) to the main input terminal.
(1) Ground wire should be connected to the UPS ground terminal;
(2) Connect the AC input cable to the terminal block
①
;
(3) Connect the four load power wires to the terminal block
② .
1. Wiring connection diagram:
2. Single power input:
1900