30
Appendix 1
Technical parameters and specifications
Remark:
EDX 60-80kVA 0.99 at full load.
-20%~+10%
default;
-24%~+15%
regulate.
ECO mode is supported by EDX 60KVA-80KVA in single and parallel machine mode.
Model EDX 60KVA EDX 80KVA
Power Rating 60KVA/48KW 80KVA/64KW
Input
Connection 3-Phase + N+G
Frequency 40-70Hz
Power factor ≥0.99
Utility voltage
range
400×(-48%~ +20%)VAC(when input voltage<72%, output power derating is
required)
Bypass Voltage
range
400×(-24%~ +15%)VAC
Output
Voltage rating
Line voltage 400×(1±1%)VAC or phase voltage 230×(1±1%)VAC(with
balanced load)
Power factor 0.8
Frequency
tolerance
50Hz±8%(track bypass frequency input ;when input frequency exceeds ±8% or
under the mode of battery power supply, frequency output should be±0.1%of
nominal)
Overload time
≥10min 110%<Load≤125%
≥1min 125%<Load≤150%
Efciency
Double-
conversion mode
Up to 94%
ECO mode Up to 98%
Operating
Environment
Ambient
temperature
0~40
Storage
temperature
–25~55
(without battery)
Ambient humidity 0-95%
Altitude ≤1000m
Nominal
battery
voltage/
Rated
charging
voltage
28 Pcs ±168VDC/±189VDC
30 Pcs ±180VDC/±202.5VDC
32 Pcs ±192VDC/±216VDC
Weight
N.W/Contain
transformer
282Kg 306Kg
G.W/Contain
transformer
356Kg 380Kg
UPS Dimension(W*D*H)(mm)
600×800×1900 600×800×1900
Safety
Standard
National
Standard
GB4943
TCL certication YD/T1095
EMS
ESD GB/T 17626.2 Level 4
RS GB/T 17626.3 Level 3
EFT GB/T 17626.4 Level 4
SURGE GB/T 17626.5 Level 4
EMI
Radiation and
Conduction
GB 7260.2
WARNING: This is a product for commercial and industrial application in the second environment-
installation restrictions or additional measures may be needed to prevent disturbances.