3.4 Requirements of wiring cables and protect device for EDX series
UPS
External batteries of EDX Series UPS require serial connection of positive and
negative for each group of 14-16 batteries (12VDC per battery) with the same
capacity, nominal voltage for each group being 168VDC-192VDC. Battery
capacity and number of groups can be selected at your option. Battery pack
must be equipped with disconnection and over-current protection facilities,
and overload and line voltage should also be taken into consideration for wire
diameter selection. Please refer to the table below for details:
Machine
Model
Rated power
Input
live wire
diameter
Output
live wire
diameter
Battery positive
/N negative
wire diameter
Ground
wire
diameter
N wire
diameter
EDX
60KVA
60kVA/48kW
2AWG/
25mm2
2AWG/
25mm2
1AWG/
35mm2
2AWG/
25mm2
1AWG/
35mm2
EDX
80KVA
80kVA/64kW
1AWG/
35mm2
1AWG/
35mm2
0AWG/
50mm2
1AWG/
35mm2
0AWG/
50mm2
Machine
Model
AC input
breaker
Bypass
input
breaker
Battery
switch
N wire
switch
AC input
fuse
Battery
input fuse
EDX 60KVA
3φ150A/
380VAC
3φ150A/
380VAC
3φ300A/
250VDC
1φ200A/
220VAC
100A
690V*2
100A 690V
EDX 80KVA
3φ175A/
380VAC
3φ175A/
380VAC
3φ400A/
250VDC
1φ250A/
220VAC
100A
690V*2
100A 690V
Remark:
1. Prior to connecting the power distribution system to the UPS, make sure a
correctly rated three-pole circuit breaker is installed.
2. When single-phase current exceeds 100A, switches of protective atmosphere
should be equipped with arc control devices,It should be D-curve air switch with
UL certication according to the customer requirement;
3. Batter
y positive/negative/N wire size: indicates UPS and battery bank wire size;
red wire signies the positive polarity and black wire the negative, while blue wire
the neutral.
4. All battery cables should be of equal length (positive, negative and N) with total
length of no more than 40m.