32
Should any display or warning message excluded in the above table be found,
please contact your distributor or call Eaton service for advice.
Indicator light is on
Indicator light ashes
Warning include one or more than one of these:
1.EPO active
2.Line loss
3.Neutral loss
4.Line phase error
5.Bypass loss
6.Bypass phase error
7.Battery open
8.Low battery voltage
9.Over charger
10.Battery reverse
11.Charger failure
12.Battery over restrict
 
Low battery voltage
   
One ash
every 1 sec
One beep
every 1 sec
 
Overload
   
One ash
every 1 sec
One beep
every 1 sec
6
Fault Mode
 
Normal
       
Long light Long beep
7
Converter Mode
 
Normal
   
None None
 
Fault
   
One ash
every 4 sec
One beep
every 4 sec
8
ECO Mode
 
Normal
 
One ash
every 1 min
None
One beep
every 1 min
 
Fault
   
One ash
every 4 sec
One beep
every 4 sec
13.Battery over temperature
14.Fan over restrict
15.BUS capacitor over restrict
16.Fan failure
17.Fan disconnected
18.Low temperature Battery
19.communication disconnected
20.Auxiliary charger failure
21.Bypass N wire cut
22.Battery N wire cut
23.Address conict
Remark:
In fault mode, output is present (supplied from bypass source) and the bypass
LED is lit (except ECO fault or output short circuit).