Maintenance
1. Storage and operating environment can affect the service life and reliability
of this product. The product is not suitable for performance in the following
environment:
2. For long-term storage, UPS (without batteries) should be kept in a dry
environment with temperature ranging from -25-55
℃
. Before start-up, ambient
temperature should be brought back to 0 or above for a certain period of time
(above 2 hours).
3. The UPS must be well ventilated to avoid internal temperature rise which will
shorten the lifetime of the components and thus shorten the lifetime of the UPS.
4. For long-term storage, the battery should be charged once every three
months in normal temperature environment and once every two months in high
temperature environment for no less than 10 hours; no-load discharge is not
allowed, and the battery continuous discharge time should not exceed 14 hours.
A. Locations where temperature or humidity exceeds the maximum or goes
below the minimum levels as shown in the technical specications (temperature
range: 0-40
℃
; relative humidity range: 0-95% non condensing);
B. Locations where vibration and impact are constant;
C. Locations where metallic dust, corrosive substances as well as salts and
inammable gases are present.