Alternatively, you can select [Device → Transfer ALL Parameters into the Device] (which
corresponds to pressing »F7« on your keyboard, or click on the small icon with many
sheets of paper and the blue arrow pointing leftward).
2. ▷
You are asked for the corresponding password, unless the required access level (in this
case: “Supervisor-Lv3”) is still open.
The settings are transferred into the device and, unless any validity or consistency
problems are detected, are being activated.
Note that PowerPort-E might also ask you whether you want to create a settings 󰊟le
containing your values, so that you are able to (re-)load all settings at a later time.
For every industry-standard commissioning work, it is always recommended to carefully
archive all changes.
CAUTION!
Clicking [Save] neither transfer nor activate any changed values (even though the
asterisk tokens disappear). The [Save] menu (and button) does nothing more than saving
your changes to a *.ErPara 󰊟le. Remember to always also transfer the parameters to the
connected device if you want to activate your changes.