This particular parameter supports Adaptive
Sets. (See ╚═▷ “Adaptive Parameter Sets” for
information, and the Technical Manual for a
detailed description.)
Select the Set which you want to modify. As a
general rule, one always starts with the Default
Set, regardless whether it is intended to also
use Adaptive Sets or not.
Operational
Info
Ack/Rst
Ok
CTRL
E_FAW
DefaultSet
ℹ If the pickup value is exceeded, the module/element starts to time out to trip. WARNING: Check the Technical Data and ensure that the actual overcurrent settings for Pickup and trip delay comply with the technical limits of the phase current inputs! (The device allows for overcurrent settings that are out of the permitted range of current values.)
Pickup
1.00 In
The previous setting value is shown. As in the
previous example, you enter the Edit Mode by
pressing the “Key” Softkey.
Operational
Info
Ack/Rst
Ok
CTRL
E_FAX
Enter Password
Prot-Lv2
*
* * *
1 2 3 4
You are asked for the password. This parameter
requires the access level “Prot-Lv2”.
Type in the digits for the password using the
Softkeys “1” … “4”, then press the »Ok« key.
Operational
Info
Ack/Rst
Ok
CTRL
E_FAY
Pickup
01.00 In
Since this is a number value you see a special
numeric editing dialog: A 󰊠ashing cursor is
underlining one of the digits, and with the
Softkeys “+” or “−” you can increase or
decrease the digit, respectively. The Softkeys
“←” (Left) or “→” (Right) move the cursor one
decimal place to the left or right, respectively.
Finally press the »Ok« key, so that this
new value gets stored (temporarily). (Or,
alternatively, press the »Ack/Rst« key to cancel
the modi󰊟cation.)
Note that again, the new value is only stored
internally, but it is not active yet.
42 www.eaton.com E-Series Family Quick Start Guide
3 Quick Start – Operation via Panel
3.7 Parameter Changes – “Ok” key