• The menu path [Control / General•
Settings] accesses the same menu branch
as the Softkey “Mode”.
• The menu path [Control] accesses the•
same menu branch as the Softkey “86”.
Operational
Info
Ack/Rst
Ok
CTRL
Starting from the Control Page, the Softkey
“Mode” takes you to the menu branch [Control /
General Settings].
There you can (re-)dene the switching
authority.
(We do not demonstrate here how to modify
a setting value. If this is not clear already, we
recommend to consult the E-Series Quick Start
Guide.)
For the »Switching Authority« setting the
following options are available:
• “None”: No control function.•
• “Local”: Control only via the buttons at the•
panel (HMI).
• “Remote”: Control only via SCADA, digital•
inputs or internal signals.
• “Local and Remote”: Control via HMI•
buttons, SCADA, digital inputs, or internal
signals.
Operational
Info
Ack/Rst
Ok
CTRL
Starting from the Control Page, the Softkey
“86” takes you into the [Control] menu, where
the connected Lockout Relays are listed.
After selecting a Lockout Relay, the Softkey “ ▶”
(Enter) takes you to the menu that is dedicated
to the selected relay. There you can make
various settings, e.g. control times, position
indicators, external switching commands.
Operational
Info
Ack/Rst
Ok
CTRL
EBR-3000_FB5
TRIP
Local
86CT 86Trip
Select
Starting from the Control Page, the Softkey
“ ▶” (Enter) takes you to an enhanced Control
Page (after you have entered the password for
access level “Control-Lv1”). The Lockout Relay
is highlighted by small markers (and in case
of both Lockout Relays being available, the
Softkey “Select” is visible, which allows you
to toggle the selected relay from one to the
other).
If the switching authority permits local
switching there are Softkeys “TRIP” and
“RESET” which allow for executing a switching
operation. (Note that usually, i. e. with correct
50 www.eaton.com E-Series Family Quick Start Guide
3 Quick Start – Operation via Panel
3.10 Control Lockout Relays via Panel – Example of a Switching Operation