Create a new Parameter File for Device Family
Select the Device Type from the list below:
E-Series Device Family
EGR-5000, Version 3.5.a
EDR-3000, Version 3.0.c
ETR-5000, Version 3.0.c
ETR-5000, Version 3.5.a
EGR-5000, Version 3.5.a
Create New Parameter File
Device Type:
EGR-5000, Version 3.5.a
Device Configuration:
Name Value
Device Model Filename:
C:\ProgramData\Eaton Relays\DeviceModels\EGR
Resulting Device Typecode:
EGR-5000A0HA
Apply
Edit
Cancel
Help
16 DI, 8+1 RO, ZI, IRIG, URTD
Phase Current 5A/1A, Standard Ground Current 5A/1A
Ethernet: IEC 61850 | Modbus TCP | DNP UDP, TCP
Fig. 4: For oine creation of a conguration le, you are rst asked for the device name and
version. After this, specify the particular device variant.
Modify Device Conguration (Typecode)
If one tries to transfer an ErPara le to a connected device which diers in its typecode (for
example: “EGR‑5000 A0HA” ErPara ⇒ EGR‑5000 A0AA) then PowerPort-E refuses to do so
with a “Type mismatch!” error message telling you that the typecodes are not the same.
In this case you can convert the settings to the typecode of the connected device. (This does
not work for dierent E-Series devices!)
Select the PowerPort-E menu »[Edit → Modify Device Conguration (Typecode)]« to open
the device variant dialog, which is essentially the same as described above (╚═▷ Fig. 4).
Here you can specify the target typecode (which should be the typecode of the connected
device, of course).
70 www.eaton.com E-Series Family Quick Start Guide
5 Conguration via PowerPort-E
5.1 Conguration File