EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Force Mode By means of this function the normal Relay Output States
can be overwritten (forced) in case that the Relay Output
is not in a disarmed state. The relays can be set from
normal operation (relay works according to the assigned
signals) to "force energized" or "force de-energized"
state.
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]
t-Timeout Force The Output State will be set by force for the duration of
this time. That means, for the duration of this time, the
Relay Output does not show the state of the signals that
are assigned on it.
Only available if: Mode = Timeout DISARM
0.00 - 300.00s 0.03s [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Force RO
/RO-4Z X2]