EDR-5000 IM02602007E
Energy Counter
ECr
Global Parameters of the Energy Counter Module
Parameter Description Setting range Default Menu path
Power Units Power Units Power Auto Scaling,
kW/kVAr/kVA,
MW/MVAr/MVA,
GW/GVAr/GVA
Power Auto
Scaling
[Operation
/General Settings]
Energy Units Energy Units Energy Auto Sca-
ling,
kWh/kVArh/kVAh,
MWh/MVArh/MVAh,
GWh/GVArh/GVAh
MWh/MVArh/MVA
h
[Operation
/General Settings]
Direct Commands of the Energy Counter Module
Parameter Description Setting range Default Menu path
Res all Energy Cr Reset of all Energy Counters Inactive,
Active
Inactive [Operation
/Reset]
Signals of the Energy Counter Module (States of the Outputs)
Signal Description
Cr Oflw VAh Net Signal: Counter Overflow VAh Net
Cr Oflw Wh Net Signal: Counter Overflow Wh Net
Cr Oflw Wh Fwd Signal: Counter Overflow Wh Fwd
Cr Oflw Wh Rev Signal: Counter Overflow Wh Rev
Cr Oflw VArh Net Signal: Counter Overflow VArh Net
Cr Oflw VArh Lag Signal: Counter Overflow VArh Lag
Cr Oflw VArh Lead Signal: Counter Overflow VArh Lead
VAh Net Res Cr Signal: VAh Net Reset Counter
Wh Net Res Cr Signal: Wh Net Reset Counter
Wh Fwd Res Cr Signal: Wh Fwd Reset Counter
www.eaton.com 189