EasyManua.ls Logo

Eaton EDR-5000 - Zone Interlocking

Eaton EDR-5000
1017 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High) 4.75 to 5.25 Vdc
Output voltage (Low) 0.0 to +0.5 Vdc
Zone In:
Nominal input voltage +5 Vdc
Max. input voltage +5.5 Vdc
Switching threshold ON min. 4.0 Vdc
Switching threshold OFF max. 1.5 Vdc
Galvanic isolation 2.5 kV ac (to ground and other IO)
Connection: Screw-type terminals (twisted pair)