EasyManua.ls Logo

Eaton EDR-5000 - Direct Commands of the Protection Module; Global Protection Parameters of the Protection Module

Eaton EDR-5000
1017 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Direct Commands of the Protection Module
Parameter Description Setting range Default Menu path
Res Fault a Mains
No
Resetting of fault number and number of grid faults. Inactive,
Active
Inactive [Operation
/Reset]
Global Protection Parameters of the Protection Module
Parameter Description Setting range Default Menu path
ExBlo Fc Activate (allow) the external blocking of the global
protection functionality of the device.
Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/Prot]
ExBlo1 If external blocking of this module is activated (allowed),
the global protection functionality of the device will be
blocked if the state of the assigned signal becomes true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Prot]
ExBlo2 If external blocking of this module is activated (allowed),
the global protection functionality of the device will be
blocked if the state of the assigned signal becomes true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Prot]
www.eaton.com 385

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals