Parameter Description Setting range Default Menu path
IX Dir Cntrl Options for direction detection. IX is used as operating
quantity.
IX 3V0,
IX Neg,
IX Dual
IX 3V0 [System Para
/Direction]
3V0 Source Earth overcurrent protection elements take into account
this parameter for direction decisions. You have to
ensure, that this parameter is set to "Measured" only if
the ground current is fed to the fourth measuring input of
the current measuring card.
Measured,
Calculated
Calculated [System Para
/Direction]
Ground MTA Ground Maximum Torque Angle: Angle between chosen
operating quantity and chosen reference quantity in case
of a ground fault. This angle is needed to determine the
ground fault direction in case of a short circuit.
Depending on the selected ground direction option,
different MTA values are used: IR 3V0, IX 3V0 : Ground
MTA; IR Neg, IX Neg : 90° + Phase MTA; IR IPol : 0°; IR
Dual : 0° (if I2 and V2 available) or Ground MTA; IX
Dual : 90° + Phase MTA (if I2 and V2 available) or
Ground MTA.
0 - 360° 110° [System Para
/Direction]