Direct Commands of the Switchgear/Breaker
Parameter Description Setting range Default Menu path
Res Bwear Sl
Breaker
Resetting the slow breaker alarm Inactive,
Active
Inactive [Operation
/Reset]
Ack TripCmd Acknowledge Trip Command Inactive,
Active
Inactive [Operation
/Reset]
Global Protection Parameters of the Switchgear/Breaker
Parameter Description Setting range Default Menu path
CinBkr-52a The breaker is in CLOSE-position if the state of the
assigned signal is true (52a).
1..n, Dig Inputs DI-8P X1.DI 5 [Control
/Bkr
/Pos Indicatrs
Wirng]
CinBkr-52b The breaker is in OPEN-position if the state of the
assigned signal is true (52b).
1..n, Dig Inputs DI-8P X1.DI 6 [Control
/Bkr
/Pos Indicatrs
Wirng]
Ready Breaker is ready for operation if the state of the assigned
signal is true. This digital input can be used by some
protective elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a trigger signal.
1..n, Dig Inputs -.- [Control
/Bkr
/Pos Indicatrs
Wirng]
Interl CLOSE1 Interlocking of the CLOSE command 1..n, Assignment
List
Wired Inputs.Bkr
Trouble-I
[Control
/Bkr
/Interlockings]
Interl CLOSE2 Interlocking of the CLOSE command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]
Interl CLOSE3 Interlocking of the CLOSE command 1..n, Assignment
List
-.- [Control
/Bkr
/Interlockings]