EDR-5000 IM02602007E
Definition of Vn:
Vn is dependent on the
»Measuring Channel«
setting in the current protection modules.
In case that this parameter is set to "Phase to Phase":
Vn=MainVT sec
In case that this parameter is set to "Phase to Neutral":
Vn=
Main VT sec
3
If the parameter
»VT con«
within the field parameters is set to
»Phase to Phase«
the setting
»Phase to Neutral«
in the current modules is effectless.
www.eaton.com 452