EDR-5000 IM02602007E
Please be aware of the meaning of the two delay timers.
t load Off (Pickup Delay): After this time expires, the load is no longer diversified.
t Max Block (Release Delay): After the starting condition is fulfilled (e.g.: breaker switched
on manually), the “CLPU.enabled” signal will be issued for this time. That means for the
duration of this time, the tripping thresholds of the overcurrent protection can be
desensitized by means of adaptive parameters (please refer to the Parameters section).
This timer will be stopped if the current falls below 0.9 times of the threshold of the load
inrush detector and remains below 0.9 times of the threshold for the duration of the settle
time.