EDR-5000 IM02602007E
Device Planning Parameters of the Cold Load Pickup Module
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Use [Device Planning]
Global Protection Parameter of the Cold Load Pickup Module
Parameter Description Setting range Default Menu path
Mode Mode Bkr State,
I<,
Bkr State Or I<,
Bkr State And I<
Bkr State [Protection Para
/Global Prot Para
/CLPU]
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/CLPU]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/CLPU]
Rvs Blo Reverse Blocking, if Reverse Blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/CLPU]
www.eaton.com 541