EDR-5000 IM02602007E
incremented shot number. In this way, the upstream feeder will “follow” the protective settings of downstream
recloser shot by shot.
For a transient fault, the autoreclose with zone coordination will not be initiated again because of absence of the fault
current and will be reset normally after the expiration of the reset timer »
t-Run2Ready«
.
www.eaton.com 573