EasyManua.ls Logo

Eaton EDR-5000 - Page 597

Eaton EDR-5000
1017 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
V< Drop Out Drop Out (is in percent of setting)
Only available if: Device Planning: V.Mode = V<
101 - 110% 103% [Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
t Tripping delay 0.00 - 3000.00s 0.00s [Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
LOP Blo Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Inactive,
Active
Active [Protection Para
/<1..4>
/Main-V-Prot
/27M[1]]
www.eaton.com 597

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals