EDR-5000 IM02602007E
RS485 - Modbus
®
RTU
Make sure that the tightening torque is 2-4 In-lb [0.22-0.45 Nm].
Terminal Marking
Pin Assignment
The Modbus
®
connection cable must be shielded. The shielding has to be fixed
at the screw that is marked with the ground symbol at the rear side of the
device.
The communication is Half Duplex.
www.eaton.com 65
1
X103
2
3
4
5
6
B(+)
A(-)
+5V GND
560
560
120
Protective Relay
HF Shield
64 5321
R1
R2
R1
+5V
GND
R1 = 560
R2 = 120
B(+)
A(-)
Protective Relay
HF Shield