EDR-5000 IM02602007E
Device Planning Parameters of the Frequency Protection Module
Parameter Description Options Default Menu path
Mode Mode Do not use,
81U-Under,
81O-Over,
81UR- Under & df/dt,
81OR- Over & df/dt,
81UDR- Under & DF/DT,
81ODR- Over & DF/DT,
81R-Rate of Change,
78V vector surge
81[1]: 81O-Over
81[2]: 81O-Over
81[3]: 81U-Under
81[4]: 81U-Under
81[5]: 81R-Rate of
Change
81[6]: 81R-Rate of
Change
[Device Planning]
Global Protection Parameters of the Frequency Protection Module
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Freq-Prot
/81[1]]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Freq-Prot
/81[1]]
ExBlo TripCmd External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Freq-Prot
/81[1]]