EDR-5000 IM02602007E
Parameter Set Parameters of the Power Protection Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
LOP Blo Measuring Circuit Supervision Voltage Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
CTS Blo Measuring Circuit Supervision Current Inactive,
Active
Inactive [Protection Para
/<1..4>
/Power-Prot
/32[1]]
Pickup P> Over(load) Active Power Pickup Value. Can be used for
monitoring the maximum allowed forward power limits of
transformers or overhead lines. Definition for VAn is as
follows: VAn = SQRT(3) * VT secondary rating * CT
secondary rating (I=1/5A) for wye or VAn = 3 * VT
secondary rating/SQRT(3) * CT secondary rating
(I=1/5A) for delta connections.
Only available if: Device Planning: PQS.Mode = Pickup
P>
0.003 - 10.000VAn 1.20VAn [Protection Para
/<1..4>
/Power-Prot
/32[1]]
www.eaton.com 691