Device Planning Parameters of the Q->&V< Module
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Do not use [Device Planning]
Global Protection Parameters of the Q->&V< Module
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Q->&V<]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Q->&V<]
V Ext Release PCC Release Signal by the Point of Common Coupling. The
line-to-line voltage is greater than 95% of VN.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Q->&V<]
PCC Fuse Fail VT Blocking if the fuse of a voltage transformer has tripped
at the PCC.
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/Q->&V<]
Power Trip dir By means of this parameter the trip direction of active
and reactive power can be inverted within the QV-Module
(sign reversal).
positive,
negative
positive [Protection Para
/Global Prot Para
/Q->&V<]
Decoupling Functions of the Q->&V< Module
Name Description
-.- No assignment
50P[1].TripCmd Signal: Trip Command
50P[2].TripCmd Signal: Trip Command
50P[3].TripCmd Signal: Trip Command
51P[1].TripCmd Signal: Trip Command
51P[2].TripCmd Signal: Trip Command
www.eaton.com 735