EDR-5000 IM02602007E
Device Planning Parameters of the Low-Voltage-Ride-Through
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Do not use [Device Planning]
Setting Group Parameters of the Low-Voltage-Ride-Through
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/LVRT
/General Settings]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/LVRT
/General Settings]
Blo TripCmd Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
Inactive [Protection Para
/<1..4>
/LVRT
/General Settings]
ExBlo TripCmd Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/LVRT
/General Settings]
Measuring Mode Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervisioned
Phase to Ground,
Phase to Phase
Phase to Ground [Protection Para
/<1..4>
/LVRT
/General Settings]
www.eaton.com 750