EasyManua.ls Logo

Eaton EDR-5000 - Page 773

Eaton EDR-5000
1017 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EDR-5000 IM02602007E
Device Planning Parameters of the BF
Parameter Description Options Default Menu path
Mode Mode Use Use [Device Planning]
Global Protection Parameters of the BF
Parameter Description Setting range Default Menu path
Scheme Scheme 50BF,
CB Pos,
50BF and CB Pos
50BF [Protection Para
/Global Prot Para
/Supervision
/BF]
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Supervision
/BF]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger Determining the trigger mode for the Breaker Failure. - . -,
All Trips,
ExP Fc,
Current Trips
All Trips [Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger1 Trigger that will start the BF Trigger -.- [Protection Para
/Global Prot Para
/Supervision
/BF]
Trigger2 Trigger that will start the BF Trigger -.- [Protection Para
/Global Prot Para
/Supervision
/BF]
www.eaton.com 773

Table of Contents

Other manuals for Eaton EDR-5000

Related product manuals