EDR-5000 IM02602007E
Within the Device Planning, set the number of required Logic Equations.
Call up the [Logic] menu.
Set the Input Signals (where necessary, invert them).
If required, configure the timer (»
On delay«
and »
Off delay«
).
If the latched output signal is used, assign a reset signal to the reset input.
Within the »status display«, the User can check the status of the logical inputs and outputs of the logic equation.
In case the logic equations should be cascaded, the User has to be aware of timing delays (cycles) in case of
descending sequences (Please refer to section: Cascading Logical Outputs).
By means of the Status Display [Operation/Status Display], the logical states can be verified.
Device Planning Parameters of the Programmable Logic
Parameter Description Options Default Menu path
No of Equations: Number of required Logic Equations: 0,
5,
10,
20,
40,
80
20 [Device Planning]