EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
VC Fund. Voltage Fundamental Magnitude in Pre State: Phase C 0.00 - 1.30Vn 0.57Vn [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
VX Fund. Voltage Fundamental Magnitude in Pre State: VX 0.00 - 1.30Vn 0.0Vn [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
Angle VA Fund. Start Position respectively Start Angle of the Voltage
Phasor during Pre Phase:Phase A
-360 - 360° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
Angle VB Fund. Start Position respectively Start Angle of the Voltage
Phasor during Pre Phase:Phase B
-360 - 360° 240° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/VT]
www.eaton.com 866