EDR-5000 IM02602007E
Parameter Description Setting range Default Menu path
Angle IC Fund. Start Position respectively Start Angle of the Current
Phasor during Pre Phase:Phase C
-360 - 360° 120° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
Angle IX meas
Fund.
Start Position respectively Start Angle of the Current
Phasor during Pre Phase: IX
-360 - 360° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
IA Fund. Current Fundamental Magnitude in Fault State: Phase A 0.00 - 40.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/CT]
IB Fund. Current Fundamental Magnitude in Fault State: Phase B 0.00 - 40.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/CT]
www.eaton.com 873