EDR-5000 IM02602007E
Name Description
BF.Pickup Signal: BF-Module Started (Pickup)
BF.Trip Signal: Breaker Failure Trip
BF.Lockout Signal: Lockout
BF.Res Lockout Signal: Reset Lockout
BF.ExBlo1-I Module Input State: External Blocking1
BF.ExBlo2-I Module Input State: External Blocking2
BF.Trigger1-I Module Input: Trigger that will start the BF
BF.Trigger2-I Module Input: Trigger that will start the BF
BF.Trigger3-I Module Input: Trigger that will start the BF
TCM.Active Signal: Active
TCM.ExBlo Signal: External Blocking
TCM.Pickup Signal: Pickup Trip Circuit Supervision
TCM.Not Possible Not possible because no state indicator assigned to the breaker.
TCM.CinBkr-52a-I Module Input State: Feed-back signal of the Bkr (52a)
TCM.CinBkr-52b-I Module Input State: Feed-back signal of the Bkr. (52b)
TCM.ExBlo1-I Module Input State: External Blocking1
TCM.ExBlo2-I Module Input State: External Blocking2
CTS.Active Signal: Active
CTS.ExBlo Signal: External Blocking
CTS.Pickup Signal: Pickup Current Transformer Measuring Circuit Supervision
CTS.ExBlo1-I Module Input State: External Blocking1
CTS.ExBlo2-I Module Input State: External Blocking2
LOP.Active Signal: Active
LOP.ExBlo Signal: External Blocking
LOP.Pickup Signal: Pickup Loss of Potential
LOP.LOP Blo Signal: Loss of Potential blocks other elements
LOP.ExBlo1-I Module Input State: External Blocking1
LOP.ExBlo2-I Module Input State: External Blocking2
AR.Active Signal: Active
AR.ExBlo Signal: External Blocking
AR.Standby Signal: Standby
AR.t-Man Close Blo Signal: AR blocked after breaker was switched on manually. This timer will be started if the breaker was
switched on manually. While this timer is running, AR cannot be started.
AR.Ready Signal: Ready to shoot
AR.Running Signal: Auto Reclosing Running
AR.t-dead Signal: Dead time between trip and reclosure attempt
AR.Bkr CLOSE Cmd Signal: Bkr. Switch ON (CLOSE) Command
www.eaton.com 974