EMR-4000 IM02602009E
Global Protection Parameters of the Analog Outputs
Parameter Description Setting range Default Menu path
Assignment Assignment 1..n,
AnalogOutputList
-.- [Device Para
/Analog Outputs
/AnOut[1]]
Range Adjustable range 0...20mA,
4...20mA,
0...10V
0...20mA [Device Para
/Analog Outputs
/AnOut[1]]
Range max Adjustable range maximum. -999999.00 -
999999.00°C
1.00°C [Device Para
/Analog Outputs
/AnOut[1]]
Range min Adjustable range minimum. -999999.00 -
999999.00°C
0.00°C [Device Para
/Analog Outputs
/AnOut[1]]
Force Mode For commissioning purposes or for maintanance, Analog
Outputs can be set by force. By means of this function
the normal Analog Outputs can be overwritten (forced).
Permanent,
Timeout
Permanent [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
t-Timeout Force The Analog Output Value will be set by force for the
duration of this time. That means for the duration of this
time the Analog Output does not show the value of the
signals that are assigned on it.
Only available if: Force Mode = Active
0.00 - 300.00s 0.03s [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
www.eaton.com 125