EMR-4000 IM02602009E
Direct Commands of the Analog Outputs
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
Force Value By means of this function the Analog Output Value can
be overwritten (forced).
0.00 - 100.00% 0% [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Analog Outputs
/AnOut[1]]
Signals of the Analog Outputs
Signal Description
Force Mode For commissioning purposes or for maintanance, Analog Outputs can be set by force. By means
of this function the normal Analog Outputs can be overwritten (forced).
www.eaton.com 126