EMR-4000 IM02602009E
Name Description
URTD.WD5 Winding 5
URTD.WD6 Winding 6
URTD.MB1 Motor Bearing 1
URTD.MB2 Motor Bearing 2
URTD.LB1 Load Bearing 1
URTD.LB2 Load Bearing 2
URTD.Aux1 Auxiliary1
URTD.Aux2 Auxiliary2
URTD.RTD Max Maximum temperature of all channels.
RTD.Hottest WD Hottest motor winding temperature in degrees C.
RTD.Hottest MB Hottest motor bearing temperature in degrees C. Resettable with "Sys Res OperationsCr" or "All".
ECr.Syst VA RMS Measured VAs (RMS)
ECr.Syst W RMS Measured Watts. Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS)
ECr.Syst VAr Fund. Measured VARs. Reactive power (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power)
(Fundamental)
ECr.Apt PF Measured Value (Calculated): 55A - Apparent Power Factor
ECr.Disp PF Measured Value (Calculated): 55D - Displacement Power Factor
ECr.VAh Net Net VA Hours
ECr.Wh Net Net Watt Hours
ECr.Wh Fwd Positive Active Power is consumed active energy
ECr.Wh Rev Negative Active Power (Fed Energy)
ECr.VArh Net Net VAr Hours
ECr.VArh Lag Positive Reactive Power is consumed Reactive Energy
ECr.VArh Lead Negative Reactive Power (Fed Energy)
www.eaton.com 128