EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
ThermBlo Fc ThermBlo Fc Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
TRN Criteria Start transition criterion TRN I,
TRN TIME,
TRN T and I,
TRN T or I
TRN T and I [Protection Para
/Global Prot Para
/MStart
/Start Control]
TRNT Motor start transition time limit
Only available if: TRN Criteria = TRN T and I Or TRN
Criteria = TRN TIME
0 - 1200s 10s [Protection Para
/Global Prot Para
/MStart
/Start Control]
TRNC Motor start transitions current level in FLA%
Only available if: TRN Criteria = TRN T and I Or TRN
Criteria = TRN I
0.10 - 3.00FLA 1.30FLA [Protection Para
/Global Prot Para
/MStart
/Start Control]
NOCS Number of cold starts limit 1 - 5 1 [Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Fc Time Between Starts on/off Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
TBS Timer Time Between Starts Limit
Only available if: TBS Fc = Active
1 - 240min 60min [Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH Fc Starts Per Hour Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
SPH SPH
Only available if: SPH Fc = Active
1 - 10 1 [Protection Para
/Global Prot Para
/MStart
/Start Control]
www.eaton.com 445