Parameter Description Setting range Default Menu path
INSQReportFrom INcomplete SeQuence report time starting point Inactive,
InSq Start2Run,
InSq Stop2Start
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
INSQReportTime INSQ Report back time
Only available if: INSQReportFrom = Active
1 - 240s 1s [Protection Para
/Global Prot Para
/MStart
/Start Control]
LAT Fc Long Time Acceleration Timer Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
LAT Timer Large motors with a high inertia may experience starting
currents that exceed the locked rotor current and time.
The protective relay has logic and provisions for a zero
speed switch input to differentiate between a stall and
start condition. If the motor is spinning then the relay will
not trip on the normal locked rotor time allowing the
motor to start.
Only available if: LAT Fc = Active
1 - 1200s 1200s [Protection Para
/Global Prot Para
/MStart
/Start Control]
ABK Fc For certain applications, such as pumping a fluid up a
pipe, the motor may be driven backward for a period of
time after it stops. The protective relay provides an anti-
backspin timer to prevent starting the motor while it is
spinning in the reverse direction. The timer begins
counting from the moment a stop is declared by the relay.
Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
ABK Timer For certain applications, such as pumping a fluid up a
pipe, the motor may be driven backward for a period of
time after it stops. The protective relay provides an anti-
backspin timer to prevent starting the motor while it is
spinning in the reverse direction. The timer begins
counting from the moment a stop is declared by the relay.
Only available if: ABK Fc = Active
1 - 3600s 3600s [Protection Para
/Global Prot Para
/MStart
/Start Control]
ZSS Zero Speed Switch Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
www.eaton.com 446