EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
EMGOVR Emergency override options. Signal has to be active in
order to release the thermal capacity of the motor. Please
notice that by doing this you run the risk of damaging the
motor. “EMGOVR” has to be set to “DI” or “DI or UI” for
this input to take effect.
Inactive,
DI,
UI,
DI or UI
Inactive [Protection Para
/Global Prot Para
/MStart
/Start Control]
RemStartBlock Remote Motor Start Blocking
Only available if: RemStartBlo Fc = Active
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
EmgOvr Emergency Override. Signal has to be active in order to
release the thermal capacity of the motor. Please notice
that by doing this you run the risk of damaging the motor.
“EMGOVR” has to be set to “DI” or “DI or UI” for this input
to take effect
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
INSQ INcomplete SeQuence
Only available if: INSQReportFrom = Active
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
ZSS Zero Speed Switch
Only available if: ZSS = Active
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
STPC Blo With this setting a Digital Input keeps the Motor in the
RUN mode, even when the motor current drops below
STPC (motor stop current).
1..n, Dig Inputs -.- [Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
t-Blo-IOC Phase Instantaneous Overcurrent Start Delay. 50P[x]
elements are blocked for the time programmed under this
parameter, while the motor is starting.
0.03 - 1.00s 0.05s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-GOC Ground Instantaneous Overcurrent Start Delay. 50X[x],
50R[x] and 50G[x] elements are blocked for the time
programmed under this parameter, while the motor is
starting
0.03 - 1.00s 0.08s [Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
www.eaton.com 447