EasyManua.ls Logo

Eaton EMR-4000 - Page 460

Eaton EMR-4000
998 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EMR-4000 IM02602009E
Device Planning Parameters of the Motor Wellnes
Parameter Description Options Default Menu path
Mode Mode Do not use,
Use
Use [Device Planning]
Global Protection Parameters of the Motor Wellnes
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
HP Horse Power 1 - 500000 500 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Num Pole Pairs Number of pole pairs of the motor 1 - 16 4 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Num Rotor Bars Number of Rotor Bars 10 - 5000 55 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Rotor Diameter Diameter of the Rotor 0.1 - 10 0.6 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
www.eaton.com 460