EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Rotor Length The Length of rotor 0.1 - 10 1.5 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
FFTBreakTime The idle time between two broken rotor bar detections -in
seconds. This time expires only, if motor is in run mode.
120 - 60000 3600 [Protection Para
/Global Prot Para
/Motor Diagnosis
/BRB Detection]
Direct Commands of the Motor Wellnes
Parameter Description Setting range Default Menu path
Trigger BRB
evaluation
Manual trigger for a broken rotor bar detection
evaluation.
Inactive,
Active
Inactive [Operation
/Count and
RevData
/Motor Diagnosis]
www.eaton.com 461