EMR-4000 IM02602009E
Global Protection Parameters of the Thermal Model
Parameter Description Setting range Default Menu path
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/49]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/49]
ExBlo TripCmd External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/49]
Use RTD values Take RTD values into account for the calculation of the
Thermal Model.__
Inactive,
Active
Inactive [Protection Para
/Global Prot Para
/49]
K2 This value represents the negative sequence current
weighting factor of the motor. The User can mimic the
behavior of the MP-3000 if this value is left to “6.01”
0.10 - 10.00 6.01 [Protection Para
/Global Prot Para
/49]
τ-cool Cooling time constant 5 - 240 60 [Protection Para
/Global Prot Para
/49]
www.eaton.com 469