EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
WD 1 Alarm Winding 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 t-Delay Winding 1 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 1 Trip Winding 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C 100°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 1]
WD 2 Alarm
Function
Winding 2 Alarm Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 Trip Function Winding 2 Trip Function Inactive,
Active
Active [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 Alarm Winding 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C 80°C [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
WD 2 t-Delay Winding 2 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min 1min [Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD 2]
www.eaton.com 717