P6 – Drive Isolation Contactor includes Drive test switch
This option is only available on the IntelliPass models. An input contactor is supplied wired to the drive input and a manual
2 position selector switch is provided to control the contactor. The switch is located inside the enclosure on the door. The
enclosure door must be opened to operate this switch. See typical IntelliPass schematic.
The contactor removes main power from the Drive. The Drive display and logic will remain active because of the separate
24Volt power supply, but the Drive will not run. The Drive Keypad is still powered and the bypass feature remains operational
and the motor can be run in bypass using the keypad. The input contactor “I” is energized at all times while in the drive
mode if the door mounted selector switch us in the on position. This option cannot be used with M1 Manual Bypass, IS
Isolation switch or P3 fuse options.
P6 Drive Isolation Contactor Option Typical View Frames 4 - 6 (FR4 Shown)
Switch on inside of door
Input contactor