Torque
Volts Hp Current
Eaton P/N
Branch protection
or Disconnect
FLA Adj
Range
Instructions
See Eaton.com
Eaton P/N
LSA Adapter
Wire range lb-in N-m Tool
208 20 59.4 HFDMP3080JL 40-80 IL29C115C N/A
14-10 35 4
Slotted
Head
25 74.8 HFDMP3080JL 40-81
30 88 HFDMP3100JL 80-100
230 20 54 HFDMP3080JL 40-80
8 40 4.5
25 68 HFDMP3080JL 40-80
30 80 HFDMP3100JL 80-100
6-4 45 5.1
40 104 HFDMP3160JL 100-160
480 50 65 HFDMP3080JL 40-80
60 77 HFDMP3080JL 40-80
3 - 4/0 50 5.6
75 96 HFDMP3100JL 80-100
HFDMP FLA DIAL setting
HFDMP A B C D E
80A 40 50 60 70 80
100A 80 * 90 * 100
160A 100 115 130 145 160
Motor Wiring
Motor connection points are identified by a label (1TA,1TB,1TC). See Output wiring table in technical section for wiring and
torque information. Also see H-Max Installation manual MN04008005E for more details on connections to drive output termi-
nals when an output contactor is not supplied.
For IntelliPass models, wire the motor leads directly to the output contactor O. Motor connections are made directly to the
bottom of the output contactor on the lower right side (see examples below)
Typical Motor
Connection
Point Label
36
Wiring
H-Max Series Drives IntelliPass®/IntelliDisconnect® IL04008003E April 2013 www.eaton.com