Input Power wiring
Input power connection are made to the disconnect device. Input power connection points are identified by Label (L1, L2 and 
L3).
Typical Input Power Connection Point Labels
Connect Input Power Wires here
Both Intellidisconnect and Intellipass provide an input disconnect by using a UL Listed, Manual Self-protected Combination 
Motor Controllers (Type E), Model XTPR or a listed molded case circuit breaker, Models HFD sized as indicated in Input 
Wiring Table. Line Side Adapter (Eaton model XTPAXLSA or XTPAXLSAD) is also provided with the XTPR Type E devices.
These devices provide a disconnect function and the IntelliPass models branch protection/short circuit protection and Class 
10 Motor overload protection while running in bypass.  These devices are factory adjusted to the nameplate value of unit- 
See Input Wiring Table.  If necessary adjust the dial for proper Motor FLA -see examples below.
If Necessary,
Set Motor FLA here
Value is Factory Set to Nameplate 
Value
See Input Wiring Table
If Necessary, Remove Operator 
Mechanism to Access Setting Dials 
to set Motor FLA 
Value is Factory Set to Nameplate 
Value See Input Wiring Table